UPS with Up to 4 Internal Battery Strings Important Safety Instructions — SAVE THESE INSTRUCTIONS Read these instructions carefully and look at the equipment…
UPS with Up to 4 Internal Battery Strings Specifications Specifications for 400 V Systems Input Specifications 400 V UPS rating 10 kW 15 kW 20 kW 30 kW 40 kW…
UPS with Up to 4 Internal Battery Strings Single System Overview UIB Unit input breaker SSIB Static switch input breaker IMB Internal maintenance breaker UOB…
UIB Unit input breaker SSIB Static switch input breaker IMB Internal maintenance breaker UOB Unit output breaker SIB System isolation breaker BB Battery…
UPS with Up to 4 Internal Battery Strings Overview of Installation Kits Installation Kit 0M-88357 Part Used in Number of units USB cable Connect the Modbus…
1. Prepare for Installation, page 36. 2. Install the Seismic Anchoring (Option), page 40. 3. Perform one of the following: – Connect the Power Cables in Single…
UPS with Up to 4 Internal Battery Strings Installation Procedure for Parallel Systems Simplified 1+1 Parallel System Parallel System 1. Prepare for…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Do not drill or punch holes for cables or conduits with the gland plate installed and do not drill or…
1. Mount the rear anchor(s) to the floor. Use appropriate hardware for the floor type – the hole diameter in the rear anchor is ø14 mm. 2. Install the rear…
UPS with Up to 4 Internal Battery Strings Connect the Power Cables in Single Mains System NOTICE RISK OF EQUIPMENT DAMAGE To ensure correct load sharing in…
UPS with Up to 4 Internal Battery Strings Connect the Signal Cables NOTE: Route the signal cables separately from the power cables and route the Class 2/SELV…
NOTE: Route the signal cables separately from the power cables and route the Class 2/SELV cables separately from the non-Class 2/non-SELV cables. Example of…
1. Connect the provided PBUS 1 (white) and PBUS 2 (red) cables to the PBUS ports in the UPS controller boxes. Route the PBUS cables through the cable channel…
UPS with Up to 4 Internal Battery Strings Connect the External Communication Cables 1. Connect the external communication cables to the ports in the UPS…
The safety labels on your product are in English and French. Sheets with translated safety labels are provided with your product. 1. Find the sheets with…
UPS with Up to 4 Internal Battery Strings Final Installation DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Batteries can present a risk of electric…