Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following…
NOTICE RISK OF ELECTROMAGNETIC DISTURBANCE This is a product category C2 UPS product. In a residential environment, this product may cause radio inference, in…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Read all instructions in the installation manual before installing or working on this product. Failure…
NOTE: Maximum short circuit rating: 10 kA RMS symmetrical. NOTE: GVSBPSU80K120H can support a load of up to 120 kW/kVA as long as the neutral current (250 A)…
Refer to the UPS installation manual for recommended upstream protection
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH All wiring must comply with all applicable national and/or electrical codes. The maximum allowable…
NOTE: Clearance dimensions are published for airflow and service access only. Consult with the local safety codes and standards for additional requirements in…
Operating Storage Temperature 0 °C to 40 °C -25 °C to 55 °C Relative humidity 5-95% non-condensing 10-80% non-condensing Elevation 0-3000 m Protection class…
Safety IEC 62040-1: 2017, Edition 2.0, Uninterruptible Power Systems (UPS) - Part 1: Safety requirements Performance IEC 62040-3: 2011-03, 2nd edition…
NOTE: In Schneider Electric literature, 'disconnect device' is used as a generic term covering circuit breakers or switches as their position may vary…
Single System – Single Mains Simplified 1+1 Parallel System – Single Mains Single System – Dual Mains Simplified 1+1 Parallel System – Dual Mains 1. Mount the…
Single System – Single Mains Single System – Dual Mains 1. Mount the Maintenance Bypass Panel to the Wall, page 19. 2. Prepare the Maintenance Bypass Panel for…
CAUTION RISK OF INJURY OR EQUIPMENT DAMAGE • Mount the maintenance bypass panel to a wall or a rack that is structurally sound and able to support the weight…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Do not drill or punch holes with the gland plates installed and do not drill or punch holes in close…
NOTE: The neutral jumper makes a bolted connection of the neutral so that the neutral is not disconnected when the 4-pole disconnect devices are opened. NOTE…
NOTE: For a simplified 1+1 parallel system, install the power cables from the two UPSs on the front and rear side of the busbar using the same bolt. 1. Connect…
1. Connect the PE cables to the PE busbar. GVSBPSU20K60H and GVSBPSU80K120H 2. Do one of the following: – For single mains: Connect the input cables from…
NOTE: Route the signal cables separately from the power cables and route the Class 2/SELV cables separately from the non-Class 2/non-SELV cables. GVSBPSU10K20H…
NOTE: The disconnect device indicator lights are supplied by UPS 1 and will only work while UPS 1 is powered. NOTE: The AUX switches are in optional parallel…
1. Remove the three disconnect device indicator lights and the disconnect device indicator light labels from the maintenance bypass panel. The disconnect…
The safety labels on your product are in English and French. Sheets with translated safety labels are provided with your product. 1. Find the sheets with…
1. Close the inner door and fasten it with the screws. 2. Add labels to the disconnect device indicator lamps, the disconnect devices, and the diagram label…
1. Shut down the UPS completely – follow the instructions in the UPS operation manual. 2. Lockout/Tagout all disconnect devices in the switchgear in the OFF…