Before installing an air conditioner, please read this manual thoroughly to ensure that you know how to safely and efficiently install a new appliance. ❋DVM S…
Outdoor unit classification Classification Small chassis Large chassis Appearance Models AM080/100/120FXWA✴ AM200FXWA✴/AM300KXWA✴ Packaging material…
Decide the installation location regarding the following condition and obtain user’s approval. Standard installation condition f Heat source water containing…
Minimum space requirement for installation f Secure minimum installation space as shown in the following figures, considering service area and path for…
f You must keep following accessories until the installation is finished. f Hand over the installation manual to the customer after finishing the…
Make sure to remove the wooden pallet before installing the outdoor unit. If you do not remove the wooden pallet, there is risk of fire during welding the…
Installing the drain pipe f Attach the drain pipe to the drain socket (PT1/2) located on the bottom of the product. Drain socket (PT 1/2) Single installation…
When installing, make sure there is no leakage. When collecting the refrigerant, stop the compressor first before removing the connection pipe. If the…
Air tightness test f Use tools for R-410A to prevent the inflow of foreign substances and resist against the internal pressure. f Do not remove the core of…
Insulating the refrigerant pipes and branch joints f Check for gas leakage before completing (the hose and pipe insulation) and if there is no sign of…
After installing the product, be sure to perform leak tests on the piping connections. Before pumping down refrigerant to inspect or relocate the outdoor unit…
f The R-410A refrigerant is blended refrigerant. Add only liquid refrigerant. f Measure the quantity of the refrigerant according to the length of the…
Step Display content Display At initial power input Checking segment display SEG 1 SEG 2 SEG 3 SEG 4 “8” “8” “8” “8” While setting communication between indoor…
You can set the MCU address, the MCU ports to use, and the address for each MCU port connected to each indoor unit. It is for 2nd-generation MCU only.…
It is recommended to use closed circuit cooling tower. If open cooling tower is applied, use intermediate heat exchanger and make sure that supplied heat…
Flow switch connection (Mandatory connection) f When flow switch is used, it will receive signal of the heat source water circulation and detects if there is…
2Way solenoid valve f When installing multiple number of outdoor units to a common water pipe, 2way valve will cut the cooling water supply to an outdoor…
1. Before supplying the power, use DC 500 V insulation resistance tester to measure the power (3 phase: R, S, T/ 1 phase: L, N) terminal and insulation…
Precautions before trial operation • When the outdoor temperature is low, turn on the main power 6 hours before beginning the operation. - If you start the…
Measures to take when an E503 error occurs (When the “inspection required” message appears on the S-NET pro report) 1. Run trial operation mode for more than…
This function detects the amount of refrigerant in the system Start Press the Tact switch "K2" 5 times Check the amount of refrigerant Judge the amount of…
Precautions on plate type heat exchanger maintenance ❋Make sure to tell the user to keep this installation manual. 1. When the product was not operated for…
1. Standard of cooling water quality for air conditioning and the number of water quality inspection ❋Make sure to comply the standard for water quality…
Model specification (Weight and dimension) Type Model Net weight Net dimension(W*H*D) Outdoor unit AM080FXWANR 160.0 kg 770*1000*545 mm AM100FXWANR 160.0 kg…