This manual provides instructions to install two configurations of the Power Distribution Panels (PDP) for the Easy Rack PDP System Cabinet. Each of the…
warnings and other precautions. Should you require any installation/operation service, parts, accessories, or maintenance, contact Schneider Electric Customer…
Upon receipt of the equipment, inspect for obvious signs of external damage. NOTE: A thorough internal inspection should be conducted only after the unit has…
PDPMIB1N-40 or PDPMIB2N-20 OR Item Description PDPMIB1N-40 Quantity PDPMIB2N-20 Quantity 1 Cable manager 1 1 2 M6 x 12 Phillips pan head screw (in accessory…
Tools Required (not provided) Cage Nut Tool Pliers Flat tip screwdriver Box cutter knife Phillips head screwdriver Wire crimping tool 990–91537 11
(not provided) Cage Nut Tool Pliers Flat tip screwdriver Box cutter knife Phillips head screwdriver Wire crimping tool 990–91537 11
Using Cage Nuts: • Locate the top and bottom U-space on the vertical mounting rails. Every third hole on the mounting rails is numbered to indicate the middle…
The PDP system is installed in an Easy Rack using Rail Kits SRVSRK1. The Rail Kits include one rail for the Left side and one rail for the Right side of the…
1. Install the cable protectors (2), grommet(s) (1), and grommet covers (4) as required for your system’s configuration into the cable access panel (3). 1N…
Install the Brackets to the PDP System Component Install the brackets from the hardware bag to the system components using the M4 x 8 Flat head screws…
Complete wiring the PDP components using the wiring diagrams in the Power Distribution Panel Electrical Diagrams Chapter in this manual. 1N Configuration Front…
Wiring from the UPS should be installed through the cable protectors in the back of the safety covers of the PDPUPS1N-40 or PDPUPS2N-20, and PDPPDU40. To do…
DANGER SHOCK HAZARD Do not operate this equipment with safety covers removed. Failure to follow these instructions will result in death or serious injury. All…
System Cabinet Preparations 1. Ensure the PDPs are properly installed in the rack. Refer to the installation instructions. 2. Ensure the PDP power cables have…
1N Maintenance Bypass Procedure This procedure is for the UPS system in the maintenance bypass-operating mode (System is on External Maintenance Bypass) with…
Problem Possible Cause Solution Ambient high temperature alarm Cooling unit does not supply cold air Ensure no alarms are indicated on the cooling unit’s Web…
PDPMIB1N-40 AC Nominal Input Voltage 3ɸ 5–Wire 400 VAC AC Input Voltage Range 380–415 VAC Power Rating 40 kW Maximum Input Breaker Current Input Voltage = 3ɸ…
for PDPMIB1N-40, PDPMIM2N-20, PDPUPS1N-40, PDPUPS2N-20, PDPPDU-40 The limited warranty provided by Schneider Electric in this Statement of Limited Factory…