Loading manual…
Loading manual…
EATON has implemented an environmental-protection policy. Products are developed according to an eco-design approach. Substances This product does not contain…
Part number Description 9PXEBM36RT2U 9PXEBM48RT2U 9PXEBM72RT2U Extended battery module 9RK Rack kit 9PX Network-MS Network card Modbus-MS Modbus and network…
The UPS has a five-button graphical LCD. It provides useful information about the UPS itself, load status, events, measurements and settings. Online mode…
After 5 minutes of inactivity, the LCD displays the screen saver. The LCD backlight automatically dims after 10 minutes of inactivity. Press any button to…
Press the Enter ( ) button to activate the menu options. Use the two middle buttons ( and ) to scroll through the menu structure. Press the Enter ( ) button to…
If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for…
Do not connect the UPS to utility until installation is completed. 3 5 2 1 4 To connect the UPS: 1. Remove the center cover of the front panel. 2. Push left…
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and will not harm personnel. Insert the EBM cable into the UPS battery…
If you ordered other UPS accessories, refer to user manuals to check the connection to the UPS. 9PXEBM48RT2U 9PXEBM72RT2U
Adjustment of the orientation of the LCD panel and of the logo. • Adjustment of the angle of vision of the LCD panel. If you ordered other UPS accessories…
Rack mounting of UPS, EBM, and accessory modules. Follow steps 1 to 4 for module mounting on the rails. 3 3 4 4 2 1 1 The rails and necessary hardware are…
Check that the indications on the name plate located on the back of the UPS correspond to the AC-power source and the true electrical consumption of the total…
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads. 9PX 2000RT MBP-120 LOAD 15 28 1 8 2 4 3 5 6…
Connection of RS232 or USB communication port The RS232 and USB communication ports cannot operate simultaneously. 9 10 17 18 1. Connect the RS232 17 or USB…
Programmable Signal Inputs The 9PX incorporates 3 programmable signal inputs: one Remote Power Off (RPO) input terminal, one Remote On/Off (ROO) input…
To start the UPS: 1. Verify that the internal batteries are connected. See "Connecting the internal battery" on page 21. 2. If optional EBMs are installed…
Automatic battery test Automatic battery tests are done every week in constant charging mode and at each cycle in ABM mode. The tests frequency can be…
For the best preventive maintenance, keep the area around the equipment clean and dust free. If the atmosphere is very dusty, clean the outside of the system…
If you store the equipment for a long period, recharge the battery every 6 months by connecting the UPS to utility power. The internal batteries charge to 90%…
Eaton UPS batteries have an expected life span of 3-5 years. After 4 years of operation, the UPS will provide a battery replacement notification reminding you…
DO NOT DISCONNECT the batteries while the UPS is in Battery mode. Batteries can be replaced easily without turning off the UPS or disconnecting the load. If…
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads. Maintenance 1. Set switch 33 to Bypass…
To check the Event log or Fault log : 1. Press any button on the front panel display to activate the menu options. 2. Press the button to select Event log or…
Input Filter AC/DC Boost DC/AC Inverter Outpout Filter Bypass DC/DC Battery Charger Table 1. Power Module model list Model Power ratings 9PX700RT 700VA / 630W…