ATS Settings 2 Measures/Infos 4 Events 2.4.1 Power flow or S1 is defined as the priority source (true by default) or S2 is defined as the priority source (can…
For Fault, refer to troubleshooting section 6.1. Event Example of displays Rootcause Overload Load is over nominal rating Remove some of the equipment from the…
Verify that the following additional items are included with the ATS: EATS16 2 3 1 8 7 4 5 6 1 User manual 2 Quick start guide 3 Safety manual printed 4 2 x…
Please store the ATS in its original package and in a dry place. Keep the storage temperature between -13 to 131°F (-25°C and +55°C). 3.3
3 2 1 3 2 Follow steps 1 to 3 for module mounting on the rails. Accessories for rack installation • 1 x Ear (Left) • 1 x Ear (Right) • 4 x M4 x 6 flat screw…
1. Elevated Operating Ambient - If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment may be greater…
RS232 communication port • Characteristics of the optocouplers communication port When a signal is activated, the contact is closed between the common (Pin 4)…
Eaton Software suite provides up-to-date graphics of ATS power and system data and power flow. It also gives you a complete record of critical power events…
Operation status Possible cause Action Overload Power requirement exceeds the ATS capacity (greater than 105 % of nominal). Remove some of the equipment from…