For Easy UPS 3M and Easy UPS 3L Important Safety Instructions — SAVE THESE INSTRUCTIONS Read these instructions carefully and look at the equipment to become…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Read all instructions in the installation manual before installing or working on this product. Failure…
For Easy UPS 3M and Easy UPS 3L Specifications NOTICE HAZARD OF EQUIPMENT DAMAGE Refer to the UPS installation manual for detailed specifications for the UPS…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH The classic battery cabinet must only be used with the Easy UPS 3M or the Easy UPS 3L. Failure to…
Easy UPS 3M 60-100 kVA UPS Commercial reference Breaker type 60 kVA 80 kVA 100 kVA Ir Im Ir Im Ir Im E3MCBC7C C25S4D + C254MG250D 175 520 (fixed) 200 520…
Easy UPS 3M 50-100 kVA UPS Commercial reference Breaker type 50 kVA 60 kVA 80 kVA 100 kVA Ir Im Ir Im Ir Im Ir Im E3MCBC7C C25S4D + C254MG250D 175 520 (fixed)…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH All wiring must comply with all applicable national and/or electrical codes. The maximum allowable…
NOTE: Clearance dimensions are published for airflow and service access only. Consult with the local safety codes and standards for additional requirements in…
NOTE: The distance between the battery bank and the UPS must not exceed 200 m. Contact Schneider Electric for installations with a longer distance. 1. Perform…
For Easy UPS 3M and Easy UPS 3L Optional Cable Kits for Line-Up Solutions Two cable kits are available: • E3MOPT003: Cable kit that includes power cables and…
NOTE: Route the signal cables separately from the power cables to ensure sufficient isolation. NOTE: Use double isolated signal cables. The signal cables must…
For Easy UPS 3M and Easy UPS 3L Connect the Signal Cables to an Easy UPS 3L NOTE: Route the signal cables separately from the power cables to ensure sufficient…
For Easy UPS 3M and Easy UPS 3L Connect the Power Cables DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Perform a total power off of the UPS before…
1. Install the provided kick plates on the front, rear, and sides of the classic battery cabinet. NOTE: Only remove the kick plates when following the…
1. Open the door(s). On the 1000 mm wide classic battery cabinet, remove two screws to open the left door. 2. Lockout/Tagout the battery breaker in the OFF…