Note: This Maintenance Bypass Panel supports two UPS units connected in parallel for redundancy (1+1) only. Front View (Interior) Q21 Terminals Terminals N N…
Note: When selecting a location for the MBP, consider the need for easy access to all switches and internal components. Note: Ensure that the selected wall is…
Refer to the below figure to determine the space requirements for the MBP. Consult local codes for any additional requirements. Ideally, install the MBP in a…
Note: All power cables must be connected on-site. External power cables are not supplied with the equipment. Note: Two communication cables (30 m) are supplied…
Caution: Anchoring bolts are not supplied. Use anchors/bolts that are suitable to support the weight of the panel. 1. Measure and mark the four mounting hole…
For local, country-specific centers: go to www.apc.com/support/contact. 990-5055-001 3
MBP One-line Diagram System Output To UPS "a" Input To UPS "b" Input To UPS "b" Bypass Input To UPS "a" Bypass Input Q5a Q5b Q3 X11 F7 Q4 Q2a Q2b X4 X9 X10…
System Output To UPS "a" Input To UPS "b" Input To UPS "b" Bypass Input To UPS "a" Bypass Input Q5a Q5b Q3 X11 F7 Q4 Q2a Q2b X4 X9 X10 Maintenance Bypass From…