Maintenance Bypass Cabinet Important Safety Instructions — SAVE THESE INSTRUCTIONS Read these instructions carefully and look at the equipment to become…
Maintenance Bypass Cabinet Specifications Maximum Short Circuit Rating The maximum short circuit rating for the maintenance bypass cabinet is 65 kA RMS…
Installation Kit 0M-100265 for 10-80 kW Maintenance Bypass Cabinet Part Used in Number of units 0W49284 signal cable Connect the Signal Cables, page 51. 1…
Installation without Conduit Box – Single Mains Installation with Conduit Box – Single Mains Installation without Conduit Box – Dual Mains Installation with…
Single Mains Dual Mains CAUTION TIP HAZARD Do not remove the transportation brackets from the maintenance bypass cabinet until it is time to anchor it to the…
Maintenance Bypass Cabinet Prepare the Maintenance Bypass Cabinet and the UPS for Cables DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Do not drill…
1. Remove the middle rear plate on the maintenance bypass cabinet. Save the nuts for installing the conduit box. 2. Remove the knockouts from the conduit box.…
Maintenance Bypass Cabinet Connect the Internal Power Cables Fasten the cables to the beam with a cable tie where marked with an (A) in the illustrations. 1.…
Maintenance Bypass Cabinet Install the Seismic Anchoring (Option) Use the optional installation kits GVSOPT002 (shipped with the UPS) and GVSOPT003 for this…
Maintenance Bypass Cabinet Connect the Power Cables in a 10-80 kW Top Cable Entry System 1. The power cables must be restrained with 3/8 nylon rope: a. Tie the…
Maintenance Bypass Cabinet Connect the Power Cables in a 100-150 kW Top Cable Entry System 1. The power cables must be restrained with 3/8 nylon rope: a. Tie…
Maintenance Bypass Cabinet Restrain the Cables Use 3/8 in nylon rope to restrain the cables. 1. Wrap the rope around the cables (a). Wrap the cables four times…
Maintenance Bypass Cabinet Connect the Power Cables in a Bottom Cable Entry System NOTE: DC cables are routed through the bottom or through the conduit box of…
1. Reinstall the left upper side plate and the transparent plate on the maintenance bypass cabinet. Left Side View of the Maintenance Bypass Cabinet 2. Only…
Maintenance Bypass Cabinet Connect the Signal Cables 1. Connect the provided Class 2/SELV signal cable 0W49283 to board 640- 4864 in the UPS as shown. Single…
1. Reinstall the upper and lower front plate. Front View of the Maintenance Bypass Cabinet 54 990-5909B-001