UPS for External Batteries Important Safety Instructions — SAVE THESE INSTRUCTIONS Read these instructions carefully and look at the equipment to become…
for 400 V Systems Input Specifications 400 V UPS rating 20 kW 30 kW 40 kW 50 kW 60 kW 80 kW 100 kW 120 kW 150 kW Voltage (V) 380/400/415 Connections 4-wire…
UIB Unit input breaker SSIB Static switch input breaker IMB Internal maintenance breaker UOB Unit output breaker BB Battery breaker Single System – Single…
UPS for External Batteries Parallel System Overview UIB Unit input breaker SSIB Static switch input breaker IMB Internal maintenance breaker UOB Unit output…
Installation Kit 0M-100883 Part Used in Number of units Spring washer Connect the Power Cables, page 83. 40 Installation Kit 0M-100917 Part Used in Number of…
1. Prepare for Installation, page 76. 2. For UPS without preinstalled power modules: Install the Power Module(s), page 80. 3. Install the Seismic Anchoring…
UPS for External Batteries Installation Procedure for Parallel Systems Simplified 1+1 Parallel System Parallel System 1. Prepare for Installation, page 76. 2.…
UPS for External Batteries Installation Procedure for Single Marine Systems 1. Install the IP22 kit GVSOPT026 on the UPS – follow the installation manual…
Simplified 1+1 Parallel System Parallel System 1. Install the IP22 kit GVSOPT026 on the UPSs – follow the installation manual provided with the kit. 2. Install…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Do not drill or punch holes for cables or conduits with the gland plate installed and do not drill or…
CAUTION HEAVY LOAD Power modules are heavy and require two persons to lift. • 20 kW power module weighs 25 kg (55 lbs). • 50 kW power module weighs 38 kg (84…
UPS for External Batteries Install the Seismic Anchoring (Option) 1. Mount the rear anchor(s) to the floor. Use appropriate hardware for the floor type – the…
NOTE: The UPS is preconfigured for TNS earthing system. NOTE: 480 V solid-grounded system (no neutral connection) using a bonding busbar will result in a…
UPS for External Batteries Connect the Power Cables DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH In single mains systems where power cables are…
UPS for External Batteries Connect the Power Cables with NEMA 2 Hole Plates DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH In single mains systems…
UPS for External Batteries Connect the Signal Cables CAUTION RISK OF EQUIPMENT DAMAGE All Class 2/SELV signal cables shall be double insulated/jacket cable and…
UPS for External Batteries Connect the Signal Cables from a Modular Battery Cabinet For installation with adjacent modular battery cabinet, use the signal…
UPS for External Batteries Connect the Signal Cables from Switchgear and Third-Party Auxiliary Products NOTE: Route the signal cables separately from the power…
UPS for External Batteries Connect the IMB Signal Cables in a Simplified 1+1 Parallel System NOTE: Route the signal cables separately from the power cables to…
UPS for External Batteries Connect the PBUS Cables CAUTION RISK OF EQUIPMENT DAMAGE All PBUS cables shall be double insulated/jacket cable and minimum rated…
1. Connect the external communication cables to the ports in the UPS controller box. Front View of the Controller Box A. Universal I/O port for built-in…
The safety labels on your product are in English and French. Sheets with translated safety labels are provided with your product. 1. Find the sheets with…
UPS for External Batteries Final Installation 1. Reinstall the top cover: a. Tilt the top cover and slide it onto the UPS from the rear. Tabs in the rear of…
UPS for External Batteries Decommission or Move the UPS to a New Location 1. Shut down the UPS completely – follow the instructions in the UPS operation…