Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following…
NOTICE RISK OF ELECTROMAGNETIC DISTURBANCE This is a product Category C3 according to IEC 62040-2. This is a product for commercial and industrial applications…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Read all instructions in the installation manual before installing or working on this product. Failure…
UIB Unit input disconnect device SSIB Static switch input disconnect device UOB Unit output disconnect device MBB Maintenance bypass disconnect device BB…
Maximum Input Short-Circuit Withstand The maximum input short-circuit withstand for the parallel maintenance bypass panel is ICC=10 kA. Recommended Cable Sizes…
Bolt size Torque M6 5 Nm M8 12 Nm
Weight kg Height mm Width mm Depth mm 10–40 kVA Parallel Maintenance Bypass Panel 30 600 550 220
NOTE: Clearance dimensions are published for airflow and service access only. Consult with the local safety codes and standards for additional requirements in…
1. Mount the Maintenance Bypass Panel to the Wall, page 16. 2. Prepare the Maintenance Bypass Panel for Cables, page 18. 3. Connect the Power Cables, page 19.…
CAUTION RISK OF INJURY OR EQUIPMENT DAMAGE • Mount the maintenance bypass panel to a wall or a rack that is structurally sound and able to support the weight…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Do not drill or punch holes with the gland plates installed and do not drill or punch holes in close…
1. Connect the PE cables to the PE busbar. Front View of the Maintenance Bypass Panel 2. Connect the input cables to the maintenance bypass switch MBB. 3.…
NOTE: Route the signal cables separately from the power cables. 1. Remove the plastic cover of the maintenance bypass switch MBB to get access to the auxiliary…
1. Shut down the UPS completely – follow the instructions in the UPS operation manual. 2. Lockout/Tagout all disconnect devices in the switchgear in the OFF…