96/160 kW 400 V Important Safety Information Read these instructions carefully and look at the equipment to become familiar with it before trying to install…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH All safety instructions in this document must be read, understood and followed. Failure to follow…
Electrical Nominal input voltage (V) 400 Nominal bypass input voltage (V) 400 Nominal output voltage (V) 400 Frequency (Hz) 50 Earthing TN-S Maximum rated…
Front View (Interior) A. Cable entry B. Q10 power supply for signals and alarms C. Communication terminal block D. Mains input terminal block E. Terminals for…
96/160 kW 400 V Site Planning NOTE: When selecting a location for the maintenance bypass enclosure, consider the need for easy access to all switches and…
Refer to the below figure to determine the space requirements for the maintenance bypass enclosure. Consult local codes for any additional requirements.…
NOTE: All power cables must be connected on site. External power cables are not supplied with the maintenance bypass enclosure. NOTE: You can cut holes for…
96/160 kW 400 V Mount the Maintenance Bypass Enclosure to the Wall CAUTION HAZARD OF INJURY Anchoring bolts are not supplied. Use anchors/bolts that are…
Front view 1. Route the cables through the top or bottom of the maintenance bypass enclosure. 2. Connect the mains input cables (L1, L2, L3, N) to the terminal…
96/160 kW 400 V Connect the Communication Cables Auxiliary contact N/O Auxiliary contact N/C Cables provided by others Cables provided by vendor 230/240 VAC…
Protective Earth (PE/G) Input/output cables provided by others 18 990–5251B–001