Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Read all instructions in the installation manual before installing or working on this product. Failure…
NOTICE HAZARD OF EQUIPMENT DAMAGE Refer to the UPS installation manual for detailed specifications for the UPS system. Failure to follow these instructions can…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH The battery circuit breaker box must only be used with the Easy UPS 3S or Easy UPS 3S Pro. Failure to…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH All wiring must comply with all applicable national and/or electrical codes. Failure to follow these…
Bolt size Torque M6 5 Nm (3.69 lb-ft) M10 30 Nm (22 lb-ft)
Weight kg Height mm Width mm Depth mm Battery circuit breaker box (E3SOPT007) 25 650 500 280
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH Place the battery circuit breaker box as close to the battery bank as possible to limit the length of…
CAUTION RISK OF INJURY OR EQUIPMENT DAMAGE • Mount the battery circuit breaker box to a wall or a rack that is structurally sound and able to support the…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Do not drill or punch holes for cables or grommets with the gland plates installed, and do not drill…
1. Loosen the screws of the inner covers and lift the inner covers up and out of the battery circuit breaker box. Front View of the Battery Circuit Breaker Box…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Perform a total power off of the UPS system before connecting the battery cables to the battery…
1. Close the inner and fasten with the three screws. 2. Close the front door of the battery circuit breaker box. 24 990-5938B-001 For Easy UPS 3S, Easy UPS 3S…
1. Shut down the UPS completely – follow the instructions in the UPS operation manual. 2. Lockout/Tagout all circuit breakers in the switchgear in the OFF…