Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following…
NOTICE RISK OF ELECTROMAGNETIC DISTURBANCE This is a product Category C3 according to IEC 62040-2. This is a product for commercial and industrial applications…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Read all instructions in the installation manual before installing or working on this product. Failure…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH • Electrical equipment must be installed, operated, serviced, and maintained only by qualified…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Battery disconnect devices must be installed according to the specifications and requirements as…
NOTICE HAZARD OF EQUIPMENT DAMAGE Refer to the UPS installation manual for detailed specifications for the UPS system. Failure to follow these instructions can…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH The battery circuit breaker kit (E3SOPT008) must only be used with Easy UPS 3S and Easy UPS 3S Pro.…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH All wiring must comply with all applicable national and/or electrical codes. Failure to follow these…
Bolt size Torque M6 5 Nm (3.69 lb-ft) M10 30 Nm (22 lb-ft)
NOTE: The illustrations in this manual shows installation in a 700 mm empty battery cabinet. The battery circuit breaker kit can also be installed in a 1100 mm…
CAUTION RISK OF EQUIPMENT DAMAGE Mount the battery circuit breaker in a grounded metal box. Failure to follow these instructions can result in injury or…
1. Install the battery breaker circuit kit in the bottom of the empty battery cabinet. Front View of the Empty Battery Cabinet 14 990-91202A-001 For Easy UPS…
1. Install the battery circuit breaker kit in the top of the empty battery cabinet. Front View of the Empty Battery Cabinet
NOTE: Route the signal cables separately from the power cables. NOTE: The illustrations in this procedure show a bottom cable entry system. The procedure is…
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Perform a total power off of the UPS system before connecting the battery cables to the battery…