Product Description Features The Schneider Electric Network Management Cards for Easy UPS, 1-Phase & 3-Phase (AP9544 and AP9547) mentioned below are Web-based…
Overview Use the Web user interface (UI) or the command line interface (CLI) to view the status of the UPS and to manage the UPS and the NMC. You can also use…
NOTE: Resetting your NMC will reset the card to its default configuration. If you forget your password, you must use the Reset button on the NMC to wipe all…
Item Description 1 10/100/1000 Base-T connector Connects the NMC to the Ethernet network. 2 USB port Support for UPS firmware updates and the optional APC USB…
Status LED This LED (light-emitting diode) indicates the status of the NMC. Link-RX/TX (10/100/1000) LED This LED indicates the network status of the NMC.…
Overview To detect internal problems and recover from unanticipated inputs, the NMC uses internal, system-wide watchdog mechanisms. When it restarts to recover…
Introduction Overview The Web user interface (UI) provides options to manage the UPS and the UPS Network Management Card (NMC) and to view the status of the…
Overview You can use the DNS name or the System IP address of the NMC for the URL address of the UI. Use your case-sensitive user name and password to log on.…
Overview Path: Home On the Home screen of the interface, you can view active alarms and the most recent events recorded in the Event Log. One or more icons and…
” • “Overview on Status menu” • “Measurements on Status menu” • “Network on Status menu” • “Maintenance on Status menu” UPS on Status menu Path: Status > UPS…
Path: Status > Overview The options below are only relevant for supported 3-Phase Easy UPS devices with an AP9547 card installed. This provides the an overview…
The options below are only relevant for supported 3-Phase Easy UPS devices with an AP9547 card installed. Path: Status > Measurements > Input Path: Status >…
Path: Status > Network The Network screen gives you your IP, domain name, and ethernet port settings. See “Network on Configuration menu”for background details…
Path: Status > Maintenance The options below are only relevant for supported 3-Phase Easy UPS devices with an AP9547 card installed. Field Description Runtime…
The options below are not available for all UPS devices. The Control menu options enable you to take immediate actions affecting your UPS, and they also have…
The options below are not available for all UPS devices. With the Configuration menu options, you can set fundamental operational values for your UPS and NMC.…
” • “UPS General screens” • “Self-Test Schedule screen” • “Shutdown on Configuration menu” • “Shutdown Scheduling” • “PowerChute Network Shutdown clients” •…
Path: Configuration > UPS Path: Configuration > UPS > Power The options below are only relevant for supported 3-Phase Easy UPS devices with an AP9547 card…
Path: UPS > Configuration > Self-Test Schedule The options below are only relevant for supported 1-Phase Easy UPS devices with an AP9544 card installed. Use…
Path: Configuration > Shutdown Use this screen to configure the parameters of a UPS shutdown. See the table below and also “Controlled Early Shutdown and End…
Path: Configuration > Scheduling The options below are only relevant for supported 1-Phase Easy UPS devices with an AP9544 card installed. NOTE: Do not create…
Specify whether to notify PowerChute clients, see “PowerChute Network Shutdown clients”. This option enables you to use the PowerChute Network Shutdown utility…
Session Management screen Path: Configuration > Security > Session Management Enabling Allow Concurrent Logins means that two or more users can log on at the…
With the Configuration menu options, you can set fundamental operational values for your UPS and NMC. See the sections below and also “Configuring your…
See these sections: • “Types of notification” • “Configuring event actions” • “E-mail notification screens” • “SNMP Traps test screen” • “SNMP Trap Receivers…
This menu deals with miscellaneous configuration items including device identification, date and time, exporting and importing your NMC configuration options…
Path: Configuration > Logs > Syslog > options The NMC can send messages to up to four Syslog servers when an event occurs. The Syslog servers record events…
Testing and calibrating Path: Tests > UPS The options below are only relevant for supported single-phase Easy UPS devices with an AP9544 card installed. With…
Using the Event and Data Logs The Event Log records individual occurrences. The Data Log, by contrast, provides you with a snapshot of your system by recording…